The CF80MAx is designed for applications requiring very low drift levels in counterflow Cooling Towers, Evaporative Cooling systems, Turbine Intake Hoods, and Scrubbers, providing the best drift removal efficiency. With field-verified drift test results of .0004% per CTI Standard 140 (the industry standard for testing of cooling tower drift), there is no need to use double layers of drift eliminators to achieve high drift-reduction efficiency.
![]() Product Weights/Span Capabilities
*Tested at a maximum of 115° F (46° C) with 2.0" (51mm) wide supports.
Drift Loss .0005% recirculation (Test Method CTI-HBIK Standard 140) is possible in new installations that are properly designed and installed and take advantage of the CF80MAx's fully-nesting design and Brentwood DriSeals. Retrofitting older cooling towers with CF80MAx Counterflow Drift Eliminators will also result in significant improvement in drift emissions. Pressure Drop Curve See CTI Technical Paper TP06-11 for comparative pressure drop tests of competing cellular drift eliminators. ![]() Materials All Brentwood Cellular Drift Eliminators are made from PVC material that meets CTI (Cooling Tower Institute) Standard 136 and are UV protected. These PVC compounds have outstanding resistance to weather exposure, and are nearly impervious to chemical degradation by alkalis and acids, grease, fats, oils, and biological attack. PVC has an excellent fire rating due to its self-extinguishing characteristics. Home | Contact | News | Cooling Tower Basics | Products | Links | Gallery Copyright © 2006 Brentwood Industries, Inc.
|
|||||||||||||||||||||||||||||||||||